GY-MT intelligent analog circuit breaker

Recommended Products
Product Details
         Technical Specification:
        1、Power supply: AC200V±10%;
        2、Tripping and closing power supply: DC220V、DC110V;
        3、Trip and close resistance selection: 400Ω、200Ω、110Ω;
        4、Closing time range:20-200ms;
        5、Trip timei range:20-100ms;
        6、Always on/ off of the analog circuit breaker contact capacity: AC220V/5A.

        Products Features:
    The circuit breaker adopts full digital circuit, and the time is set by digital dialing. It can
    realize the functions of analog circuit breaker tripping and closing time setting, three-phase /
    split phase operation        selection, input signal logic control, etc., so as to simulate the
    circuit breaker tripping and closing action.
   1. The power supply voltage of this instrument is DC220V and DC110V, the voltage must
        be consistent with the input voltage before the test;
   2. This simulated circuit breaker can simulate split-phase operation circuit breakers, and
       can also simulate three-phase operation circuit breakers. The choice of tripping and closing
       impedance is 400 ohms, 200 ohms, and 110 ohms. When simulating split-phase operation
       circuit breakers, its The tripping input terminals are A close, A trip, B close, B trip, C close,
       and C trip; when the three-phase operation circuit breaker is simulated, the tripping input
      terminals are three trips and three closes. In addition, there are manual closing and manual
      tripping buttons on the panel, and there are tripping and closing signal lights, which are three
      red signal lights of A close, B close, and C close, and three green signal lights of A trip, B trip,
      and C trip.  When simulating a three-phase operation circuit breaker, the three-phase signal
      lights of A, B, and C simultaneously turn off and on;
   3. Relays A, B, and C each output a set of switching contacts in the analog circuit, and the
      contacts with dynamic break contact closed or open contact disconnected are completely
      isolated from the operating power supply and can be relayed from the microcomputer
     cooperating with protection test equipment;
   4. The analog circuit breaker can simulate the tripping and closing time, the time setting is
      set by the DIP switch, and the precision is high. The setting range of trip time is 20-200ms,
      and the setting range of closing time is 20-100ms.
 
 